Applications
PolyPro is a polypropylene vent pipe for use with ANSI Category II and IV gas-burning appliances, including highefficiency water heaters, condensing boilers and warm air furnaces. Poly Pro is listed by Intertek to the ULC S636 standard in Canada as a Class IIA, IIB and IIC vent system suitable for exhaust temperatures up to 230°F / 110°C, and a maximum positive pressure of 15 in-w.c.
Materials and Construction
Rigid pipe constructed of 2.2mm (minimum) thick polypropylene. Flex is double-wall polypropylene. EPDM or Viton gaskets.
Clearances
0" clearance to combustibles for exhaust temperatures up to 194°F / 90°C, and 0" clearance for vertical installations up to exhaust temperatures of 230°F / 110°C and ¼" / 6mm clearance to combustibles for horizontal installations at exhaust temperatures up to 230°F / 110°C . PolyPro concentric vent system components, including concentric Horizontal Termination and Vertical Termination, are listed at 0" clearance to combustibles for exhaust temperatures up to 230°F / 110°C.
Diameters
2" (60mm), 3" (80mm), 4" (100mm), 5" (130mm), 6" (150mm), and 8" (200mm).
2"×4" (60mm×100mm), 3"×5" (80mm×130mm), 4"×6" (100mm×150mm)
Listings
Listed with the appliance in the USA, check with appliance manufacturer. Intertek / ETL listed to ULC-S636 Listed as a Class IIA, IIB, and IIC vent system.
Previously the CSA certification trademark was shown in error in conjunction with the PolyPro product - references have been removed.
Refer to our Typical Venting Installation drawings to select the appropriate component parts for your installation.